Potter PFC-3002T

Conventional 2 Zone Fire Panel

Condition: New
Brand: Potter
Status: Obsolete
SKU: 45322
Manufacturer Part #: PFC-3002T
Secondary Part #: 3002002

Description

The PFC-3002T panel is designed for non-coded fire alarm systems in small commercial, institutional and industrial occupancies.

The PFC-3002T includes one circuit board providing all the essentials for a complete fire alarm system. Two Class ‘B’ initiating circuits and one Class ‘B’ indicating circuit are provided by the PFC-3002T. The indicating circuit is protected from shorts by self-restoring circuitry.

Supervision includes ground fault detection, battery low level or open wire fault, initiating and indicating circuit wiring faults and loss of A.C. power. Initiating circuits are supervised for opens and ground faults. Indicating circuits are supervised for opens, shorts and ground faults. LED indicators are provided for Zone Alarm, Zone Trouble, A.C. On, Battery Fault, Ground Fault, Common Trouble, Signal Trouble and Signal Silenced. Switches are provided for Zone disconnect/silence, trouble silence and reset.

The PFC-3002T has selectable audible tones which can be configured via DIP switches for Steady and Temporal Code.

The panel also includes a common alarm relay which is configurable (via jumper) to follow the signal circuit or lock on until the alarm has been reset.

The controls are behind a durable locked door. The cabinet will accommodate a 4 or 8 AH battery pack.

Additional information

Weight 16 lbs
Manufacturer

Potter Electric Signal Company, LLC

Brand

Condition

New

Unit of Measurement

EA (Each)

Color

Red

Production Status

Obsolete

Features

  • Two Class ‘B’ initiating circuits
  • One Class ‘B’ indicating circuit
  • Individual Zone Silence/Disconnect switches
  • Powerful 3mA capacity per zone for 2-wire smoke detectors
  • Common alarm Relay contact, Form C, 28 VDC @ 3 AMP (Resistive)
  • Selectable ‘N.O’or ’N.C’ common trouble contact 28 VDC @ 3 Amp (Resistive)
  • A.C. ON LED (Green)
  • Zone Alarm LED (Red)
  • Signal Trouble LED (Amber)
  • Ground Fault LED (Amber)
  • Battery Fault LED (Amber)
  • Alarm Silenced LED (Amber)
  • Common Trouble LED & Silence switch
  • Remote Trouble Indicator output
  • Remote A.C. On output
  • Selectable 1 minute Signal silence inhibit
  • Extensive Transient Protection on all circuits
  • Exterior color: Red or Beige
  • All circuits are power limited

Reviews