Simplex 4098-9714

$27.80

TrueAlarm Photoelectric Smoke Sensor

Availability: In Stock

Condition: New
Brand: Simplex
Status: Active
SKU: BD02A-4885
Manufacturer Part #: 4098-9714

Description

TrueAlarm photoelectric sensors use a stable, pulsed LED light source and a silicon photodiode receiver to deliver consistent and accurate low power smoke sensing. Three user selectable sensitivities for special applications are available for each individual sensor, 0.2%, 0.5%, and 1% per foot. Standard sensitivity is 1.25% to 3.1% per foot. The fire alarm control panel runs an algorithm that can vary the sensitivity for normal applications between 1.25% and 3.1% per foot.

Note: Fixed sensitivity settings higher than 1.0% per foot are not UL268 7th Edition compliant.

The sensor head design provides 360° smoke entry for optimum response to smoke from any direction. Due to its photoelectric operation, air velocity is not normally a factor, except for impact on area smoke flow.

Additional information

Weight 0.20 lbs
Dimensions 4.875 × 4.875 × 2.125 in
Manufacturer

Johnson Controls

Brand

Condition

New

Unit of Measurement

EA (Each)

Production Status

Active

Type

Detector

Style

Plug-In

Detectable Medium

Smoke

Detection Method

Photoelectric

Programming

Set via Base

Protocol

IDNet, MAPNET II

Voltage

24 VDC

Voltage Range

18 – 32 VDC

Series

Features

  • Sealed against rear air flow entry
  • Interchangeable mounting
  • EMI/RFI shielded electronics
  • Photoelectric technology sensing
  • 360° smoke entry for optimum response
  • Built-in insect screens

Reviews

There are no reviews yet.

Be the first to review “Simplex 4098-9714”

TrueAlarm Analog Sensing

Download

Simplex - Data Sheet