Advanced AX-LPD module provides SLC and NAC circuit expansion of an existing AX-CTL-2 Intelligent Fire Alarm Control Panel. The module provides two Style 4 or Style 6/7 Signaling Line Circuits (SLCs) and two notification appliance circuits (NACs). Communications to field devices attached to the SLCs is via an advanced, 100% digital protocol with advantages of being highly immune to noisy environments and will operate over non-shielded cable without causing interference problems with sensitive electronic equipment. The NAC circuits are filtered and regulated, capable of being wired Class A or B, each rated 2 Amp @ 24 VDC. Due to exceptional regulation and high rating, the NAC outputs provide compatibility with virtually any Listed notification appliance.