Description
The Tyco Model ACC-1 dry pipe accelerator attaches to the Tyco Model DPV-1 dry pipe valve to allow faster valve operation. It automatically adjusts to both small and slow changes in system pressure, but it trips when there is a rapid and steady drop in pressure (like during a sprinkler operation). Upon tripping, the accelerator transmits system air pressure to the intermediate chamber of the Model DPV-1 dry pipe valve. This neutralizes the differential pressure holding the Model DPV-1 dry pipe valve closed and permits it to open. The ACC-1 has a unique, positive action; an internal anti-flood device; and a ball float that combine to prevent water and water-borne debris from entering the more sensitive operating areas of the accelerator.