Model PAD-5-CDC is the Conventional Zone Module used with PAD-5 notification-extender units. Specifically, each Model PAD-5-CDC supports four (4) `Class A’ or four (4) `Class B’ conventional-detection zone-input circuits. The address for Model PAD-5-CDC must be the next sequential (numerical) address to that of the connected Model PAD-5-MB main board. Up to 30 Siemens conventional smoke detectors are supported, per zone.
All information, per circuit, is displayed from the Operating Unit of the Siemens Modular FACP. Each Model PAD-5-CDC supports Siemens and other-branded smoke detectors, as well as one (1) beam detector per zone. Additionally, Model PAD-5-CDC provides optional alarm verification by circuit, as well as consistent ground fault detection.