Fike 10-063-1-R-1

$950.49

SHP-Pro Fire Alarm and Fire Suppression Releasing Control Panel; All Modes, Red Enclosure, 120V Operation

Availability: Estimated 6 - 8 Weeks

Condition: New
Brand: Fike
Status: Active
SKU: 65522
Manufacturer Part #: 10-063-1-R-1

Description

The Fike SHP Pro is a compact, cost-effective, conventional fire alarm and suppression releasing panel. The SHP Pro is designed for use with Fike Clean Agent Fire Suppressant, CO2, sprinkler (preaction/deluge), or other industrial solenoid-based suppression systems. The SHP Pro controller is shipped from the factory pre configured for Clean Agent suppression operation.

Additional information

Weight 15 lbs
Dimensions 21.00 × 14.35 × 4.00 in
Manufacturer

Fike Corporation

Brand

Condition

New

Unit of Measurement

EA (Each)

Production Status

Active

Model

Type

Control Panel

Style

Conventional

Compatibility

Listings & Approvals

City of New York, CSFM, FM, Hong Kong, OSHPD, UL

Features

  • Ten system status LEDs (AC Normal, Alarm, PreDischarge, Release, Supervisory, Trouble, Panel Silenced, Abort, Release Disabled, Ground Fault)
  • General Alarm, Supervisory and Trouble relays
  • Dip‐switch panel configuration
  • Seven segment system status and diagnostic LED
  • Local sounder (piezo) with distinct event tones
  • Reset and Silence switches
  • Disable switch for audible, releasing and relays (hardware disconnect)
  • Alarm and Trouble silence resound (after 18 hrs.)
  • Five selectable abort types
  • Gentex or System Sensor sync protocol
  • Twenty event history buffer
  • Audibles selectable for slow, fast, continuous operation
  • Integral 24 VDC power supply, 1A standby/4A alarm
  • 120/240 VAC at 50/60 Hz power input
  • Resettable and non‐resettable 24 VDC power output
  • Battery and ground fault supervision
  • 7 – 40 AH battery charging capacity
  • Carbon steel enclosure, red or gray finish, 21”H x 14.35”W x 4”D, surface or flush mountable
  • Lockable door with viewing window
  • Enclosure can hold up to two 18 AH batteries
  • Two Class B detect circuits capable of sequential, cross‐ zone, or single detector release operation.
  • Maximum 25 detectors per detect circuit, 50 total.
  • Detect circuits are compatible with select System Sensor or Hochiki conventional detectors and bases
  • Detect circuits are compatible with linear heat detection cable or contact closure type devices
  • Three Class B input circuits for monitoring closed contact devices
  • Three Class B audible circuits for NAC devices, rated 2A per circuit
  • Agent Release circuit, six ARMs/IRMs maximum, any combination
  • Solenoid circuit, one 24V or two 12V solenoids. See Fike document 06‐186 for compatible devices.