Fireye MECD1

$84.38

Cadmium sulfide amp, 0.8 sec FFRT. Use with C554A scanner

Availability: Please Call for Availability

Condition: New
Brand: Fireye
Status: Active
SKU: 180135
Manufacturer Part #: MECD1

Description

The Fireye MEUV1, MEUV4, MEUVS1, MEUVS4, MERT1, MERT4, MEIR1, MEIR4, MECD1, and MECD4 are Amplifier Modules used with the Fireye Modular MicroM control. These amplifier modules provide flame scanning capabilities using any of the Fireye standard ultraviolet scanners, self-check scanners, infrared scanners, cadmium sulfide scanners, and flame rods. The Flame Failure Response Time (FFRT) of the control is determined by the selection of the amplifier module (see Ordering Information). Test jacks are provided on the amplifier modules to permit flame signal measurement during operation and are uniform 0-10 vdc for all models.

After scanner selection, the proper amplifier module must be used in the Modular MicroM chassis (see Ordering Information). The amplifier module incorporates a plug-in design for ease of installation. The programmer module determines the operational characteristics of the control (e.g. relight, purge timing, etc.).

Additional information

Weight 0.3 lbs
Dimensions 5.75 × 4.00 × 1.75 in
Manufacturer

Fireye

Brand

Condition

New

Unit of Measurement

EA (Each)

Production Status

Active

Reviews

There are no reviews yet.

Be the first to review “Fireye MECD1”

MicroM Amplifier Modules

Download

Fireye - Manual