Fireye MEDC2

$104.96

Amplifier for use with dry contact input from 85UVF-WR flame scanner, 0.30 sec FFRT. Use with MEP237 and 85UVF4-1QDWR, 85IRF4-1QDWR, or InSight scanner (with 59-497-020WR cable)

Availability: Please Call for Availability

Condition: New
Brand: Fireye
Status: Active
SKU: 180138
Manufacturer Part #: MEDC2

Description

The Fireye MEUV1, MEUV4, MEUVS1, MEUVS4, MERT1, MERT4, MEIR1, MEIR4, MECD1, and MECD4 are Amplifier Modules used with the Fireye Modular MicroM control. These amplifier modules provide flame scanning capabilities using any of the Fireye standard ultraviolet scanners, self-check scanners, infrared scanners, cadmium sulfide scanners, and flame rods. The Flame Failure Response Time (FFRT) of the control is determined by the selection of the amplifier module (see Ordering Information). Test jacks are provided on the amplifier modules to permit flame signal measurement during operation and are uniform 0-10 vdc for all models.

After scanner selection, the proper amplifier module must be used in the Modular MicroM chassis (see Ordering Information). The amplifier module incorporates a plug-in design for ease of installation. The programmer module determines the operational characteristics of the control (e.g. relight, purge timing, etc.).