Description
The Honeywell TC810R1024 is an intelligent addressable relay module designed for use on Honeywell FlashScan Signaling Line Circuits (SLC). It provides two Form-C dry contacts that switch together, enabling control of auxiliary equipment such as fans, dampers, door holders, and air handling units.
The module is powered directly from the two-wire SLC loop and features built-in type identification for automatic recognition by the fire alarm control panel. Addressing is set using dual rotary switches, supporting up to 159 addresses on FlashScan loops (99 on CLIP loops). An integral LED blinks green during polling and illuminates steady red when activated.
The TC810R1024 mounts to a standard 4-inch square electrical box and is suitable for general fire alarm control applications requiring addressable dry-contact outputs.



Reviews
There are no reviews yet.