Secutron MR-401R

Intelligent Fire Alarm Control Panel, Red door

Condition: New
Brand: Secutron
Status: Active
SKU: 115520
Manufacturer Part #: MR-401R

Description

The MR-401 Addressable Fire Alarm Control Panel is an intelligent addressable multi-zoned panel, ideal for small to medium jobs.

The MR-401 is shipped pre-assembled with mainboard, power supply, black backbox, and red door enclosure. Compatible with MGC Devices (MIX-4000 Series), the

MR-401 can have up to three addressable (SLC) loop with a maximum of 720 MGC devices in total.

The MR-401 is equipped with a built-in dialer. The dialer provides a means to communicate panel status to the remote central monitoring station using two dedicated phone lines.

Additional information

Weight 16 lbs
Brand

Condition

New

Production Status

Active

Features

  • Main Board, Power Supply and Backbox.
  • One on-board addressable (SLC) loop for MGC Devices (MIX-4000 Series), 240 devices per loop.
  • Expandable to three addrassable loops for a maximum of 720 MGC devices (MIX-4000 Series), 240 devices per loop.
  • Multi-zone fire alarm control panel
  • Compatible with MGC devices (MIX-4000).
  • Compatible with conventional detectors using MGC MIX- 4042 Conventional Zone module, refer to document LT-1023SEC for compatible detectors.
  • Main 4 x 20 LCD display.
  • Class A (DCLA), Class X (DCLC), or Class B (DCLB) analog loop(s).
  • Four Power Limited Class B, Class A NAC circuits (max 1.5 Amps each – 6.0 Amps total).
  • NAC circuits may be configured as silenceable signal, non-silenceable signal, silenceable strobes, non-silenceable strobes, or relay output. The audible signal may be Steady, Temporal Code, California Code, or March Time.
  • Supports sync strobe protocols from major manufacturers.
  • Software configuration.
  • Configurable Signal Silence Inhibit, Auto Signal Silence, and One-Man Walk Test.
  • Two-stage, alarm verification, and positive alarm sequence operations.
  • Subsequent Alarm, Supervisory, Monitor and Trouble operation.
  • Dedicated common alarm, supervisory, trouble, and auxiliary alarm relays.
  • Additional RAX-1048TZDS Display Adder Module can be added to provide 96 annunciation points per Adder.
  • Relay Contacts for Common Alarm, Common Supervisory and Common Trouble all non disconnectable and Auxiliary Alarm Relay (disconnectable).
  • Additional outputs include connections for a RTI remote trouble indicator, PR-300 Reverse Polarity Module, an RS- 485 bus for connection of up to seven RAX-LCD-LITEs, RAM- 3500-LCDs, MR-2312-SR12s and RA-1000 Series annunciators.
  • Auxiliary power is available in the form of 24V FWR unfiltered and unsupervised, 24VDC filtered and regulated, and resettable auxiliary power supply.
  • Built-in Dialer.