Description
The 60-2947 Modernization Adapter will allow the removal / replacement of an existing E110 flame safeguard control with the Fireye BurnerLogix control in a plug and play fashion. This avoids the need for significant electrical rewiring cost and time. The BurnerLogix control will be able to re-use the existing flame scanner provided the correct BurnerLogix control is selected.
The 60-2947 consists of an adapter plate that mounts onto the existing E110 wiring base (60-1386-2 or 60-1466-2), a BurnerLogix wiring base, and an umbilical cord approximately 1.5 feet long connecting the two. If the height of the adapter will not allow the panel door to close, the BurnerLogix wiring base can be removed form the adapter plate and mounted elsewhere inside the control cabinet.
Two (2) Phillip head screws located in the upper left hand and lower right hand corners secure the BurnerLogix wiring base to the adapter plate. The total height of the 60-2947 modernization adapter and BurnerLogix control mounted on the E110 wiring base is approx. 8.25”. The 60-2947 adapter allows the user to remove the front plate of the BurnerLogix wiring base and measure voltage on the various terminals without removing the control from the base.