Description
The Fireye EP160, EP161 (extended MTFI), EP163 (programmable), EP170, and EP174 (early spark termination), EP165, EP166 (pilot stabilization), or EP177 (early spark termination and programmable operating parameters) programmer modules are utilized with the FLAME-MONITOR Burner Management Control System (P/N’s E100 and E110). Several operational characteristics of the programmer are determined by six (6) dip switches located on the side of the programmer. These characteristics include forced blower motor start delay (dip switch 1), extended purge timing (dip switches 3, 4, 5), and the option requiring the 3-P running interlock circuit to be proven open at the start of the operating cycle (dip switch 6). Dip switch 2 is inactive. Models EP163 and EP177 characteristics are programmed via the ED510 Display Module, rather than by dip switch.
The EP160, EP161, EP163, EP165, EP166, EP170, EP174, and EP177 programmers provide start-up programming, safe-start check, and flame monitoring supervision. They ensure open damper (high purge) pre-purge, proof of low fire position, and fuel valve end switch safety checks. A running interlock circuit on the FLAME-MONITOR system constantly monitors the limit switches, air flow switches, and fuel pressure switches through the programmer. The programmer control is designed to initiate a safety lockout if any of these circuits are open at the improper point in the control cycle.
Reviews