Description
The Fireye EP260, EP270 (early spark termination), or EP265 (pilot stabilization) programmer modules are utilized with the FLAME-MONITOR Burner Management Control System (P/N E110). Several operational characteristics of the programmer (with Engineering code 28 or later, e.g. 9414-28) are determined by six (6) dip switches located on the side of the programmer. These characteristics include extended purge timing (dip switches 3, 4, 5), and the option requiring the 3-P running interlock circuit to be proven open at the start of the operating cycle (dip switch 6). Dip switches 1 and 2 are inactive.
The EP260, EP265, EP270 programmers provide start-up programming, safe-start check, and flame monitoring supervision. They ensure proof of low fire position, and fuel valve end switch safety checks. The control is designed to initiate a safety lockout if any of these circuits are open at the improper point in the control cycle. A running interlock circuit on the FLAME-MONITOR system constantly monitors the limit switches, air flow switches, and fuel pressure switches through the programmer. The programmer will recycle if the running interlock circuit (3-P) is opened during the firing cycle.
Reviews
There are no reviews yet.