• When energized, the V4062 Actuator opens the V5055/ VE5000/V5097 Gas Valve to the low-fire position. The actuator opens the valve to the fully open position when the line voltage contacts are made.
• When used with the V5055, V5097 or VE5000a Gas Valve, the combination is rated for final safety shutoff service. Although the V4062 can be used with all V5055 or V5097 Valve models, the V5055/V5097B with characterized guide is recommended for optimum control and low-fire repeatability.
• The standard model has an opening time of 26 seconds at 60 Hz, or 32 seconds at 50 Hz. A fast-opening model is available, with timings of 13 seconds at 60 Hz, or 16 seconds at 50 Hz.
• Maximum closing time is one second, which meets code, standard, insurer requirements.
• Damper shaft models are available with or without spring return; shaft extends out both sides and rides in Delrin bushings; used with standard damper crank arm (part no. 7616BR).
• Red OPEN indicator attached to the actuator stem shows when the valve is even slightly open; yellow SHUT indicator on the valve stem shows only when the gas valve is fully closed.
• Ambient temperature range is -40° to 150°F (-40° to 66°C) for 60 Hz models; -10° to 158°F (23° to 70°C) for 50 Hz and 50/60 Hz models.
• Models available with factory adjusted, field-adjustable, single-pole-double throw (spdt) auxiliary switch rated at 1/2 hp (0.37 kW). Auxiliary switch can be added in the field.
• Low-fire position is adjustable with adjusting wrench, part no. 135796 (included with the actuator).
• Standard enclosure meets NEMA 1 (IP30) general purpose requirements.
• V4062/V5055C,E and V4062/V5097C, E combinations available with a proof-of-closure switch and double valve seal (valve seal over travel interlock) to meet specific code/ standard/insurer requirements.
• Model available to be used with series 60 floating type controller.
• Model available with adjustable maximum flow switch.