Description
The wireless detectors are intelligent (addressable) detectors that provide secure, reliable communication to the Fire Alarm Control Panel (FACP) across a Class A mesh network. Wireless detectors create an opportunity for applications where it is costly (concrete walls/ceilings, buried wires), obtrusive (surface mount conduit), or possibly dangerous (asbestos) to use traditional wired devices. In addition, both wired and wireless devices can be present on the same FACP, providing an integrated wired/wireless solution for increased installation potential.
The SWIFT detection line includes a photoelectric, Acclimate®, standard fixed heat, and rate‐of‐rise heat detectors. The photoelectric detectors transmit a digital representation of smoke density through a wireless mesh to a gateway and then to the FACP. The Acclimate detectors combine a photoelectric chamber and a 135°F fixed temperature heat detector. Acclimate can also transmit an alarm signal due to heat per UL 521. The fixed heat detector and rate‐of‐rise detectors utilize sensors designed for open area protection with 50‐foot spacing capability as approved by UL 521.