Description
AGF CORRinSITE Corrosion Monitors provide a practical and inexpensive method for detecting internal pipe corrosion in wet and dry pipe fire sprinkler systems. CORRinSITE Model 7700 and Model 7800 are designed to monitor actual wall loss under normal operating conditions because they install directly into the piping system and not into an isolated loop. Once installed in the wet or dry system the monitor’s plug corrodes at the same rate as the pipe. When the plug corrodes beyond it’s 0.04” limit, moisture penetrates the sealed chamber and transforms the sight glass from bright white to fluorescent orange. If the sight glass is orange the pipe needs to be inspected for internal corrosion issues.