Description
The FPA‐1000 Analog Addressable Fire Panels are a scalable solution for fire detection. Protect your small office with a single system or connect multiple panels together as your needs grow. Networking capabilities support the monitoring of up to 8 interconnected panels (2,000 addressable points) in one system for campuses or other large commercial environments. The FPA‐1000 panels combine complete built-in Fire Alarm Control Panel (FACP) equipment such as Notification Appliance Circuits (NACs), Signaling Line Circuits (SLCs), relays, power supply, Digital Alarm Communicator Transmitter (DACT), and Ethernet connection with expandability using the option bus or plug‐in boards. The two integrated NACs can be expanded with remote addressable NAC power boosters and programmed with specific activation patterns.
The control panel includes one SLC that supports 254 addressable points (254 analog detectors or modules, or 127 analog sounder bases in combination with a suitable detector). The control panel is easily expandable with the FPE‐1000‐SLC Signaling Line Circuit Plug-in Module, doubling the address points to 508.
The panel has a compact and solid metal housing with a keyed lock and a removable dead front door to access electronics. It features surface and semi-flush mounting options. On the front of the panel, six light- emitting diodes (LEDs) show Fire, Carbon Monoxide (Gas) Alarm, Power, Supervisory, Silenced, and Trouble conditions. The built‐in keypad can be used for total system control and programming even when wearing fireman gloves. In addition, a large 4‐line by 20‐character alphanumeric LCD display shows programmed device point information. Four keys enable Drill, Reset, Silence, and Acknowledge functions.
Reviews
There are no reviews yet.