Description
Edwards intelligent modules are engineered to deliver high-performance features, superb reliability, and unbeatable quality. From control of ancillary equipment, to enhanced signaling functionality, these products add flexibility and powerful options to Edwards Signaling intelligent systems.
The E-IDC1B connects a normally open, alarm, supervisory, or monitor type dry contact initiating device circuit (IDC) to the Edwards Signaling control panel. This module is for Class B circuit operation.
The device address is set using the two rotary switches located on the front of the module. One device address is required.
The module is configured to operate as an alarm latching device type from the factory. When the NO contact of an initiating device is closed, an alarm signal is sent to the control panel and the alarm condition is latched at the module.
Note: Additional device types are available through front panel programming or the configuration utility. Refer to applicable control panel technical reference manual.