Description
The Universal Valve Operator (UVO) provides means to electrically or manually activate the Fike ProInert Valve inert gas cylinder by providing the force required to extend a piston that will open the valve, allowing the agent to be released from the cylinder.
The UVO can be activated electrically via a signal from a control panel or manually by depressing red manual strike button.
Fike’s Inert Gas Cylinder with ProInert Valve / UVO can be connected directly to the solenoid circuit of SHP-Pro or to the solenoid output of the RCM on the Cheetah Xi & Cheetah Xi 50 control panels. This wiring connection will be supervised for open and ground fault conditions from the container to the control panel.