Description
The FIK‐CZ‐6 is an addressable zone interface module for use with the Fike FCP Series fire alarm control panels (FACPs). The FIK‐CZ‐6 provides six‐zone inputs that allow a Fike FACP to interface and monitor two‐wire conventional smoke detectors. This means you can retrofit an existing building and use existing conventional devices.
The inputs on the FIK‐CZ‐6 share a common FACP signaling line circuit (SLC) input and the initiating device circuits share a common external power supply. Otherwise, each input on the module operates independently from the others. If needed, you can disable a maximum of two unused inputs on the FIK‐CZ‐6 board.