Notifier N-ANN-100

$541.96

80 Character LCD Remote Fire Annunciator

Availability: Estimated 6 Weeks

Condition: New
Brand: Notifier
Status: Active
SKU: 40899
Manufacturer Part #: N-ANN-100

Description

The N-ANN-100 annunciator is a backlit, 80-character LCD fire annunciator that mimics the Fire Alarm Control Panel (FACP) display. It provides system status indicators for AC Power, Alarm, Trouble, Supervisory, and Alarm Silenced conditions.

The N-ANN-100 and the FACP communicate over a two-wire serial interface employing the ANN-BUS communication format. Connected devices are powered, via two additional wires, by either the host FACP or a remote UL-listed, filtered power supply.

The N-ANN-100 displays English-language text of system point information including device type, zone, independent point alarm, trouble or supervisory status, as well as any custom alpha labels programmed into the control panel. It includes control switches for remote control of critical system functions. (A keyswitch prevents unauthorized operation of the control switches.)

Up to eight N-ANN-100s may be connected to each ANN-BUS of a FACP. No programming is required, which saves time during system commissioning.

Additional information

Weight 2 lbs
Dimensions 12.25 × 11.50 × 3.00 in
Manufacturer

Honeywell

Brand

Condition

New

Type

Annunciator

Color

Black

Production Status

Active

Features

  • Listed to UL Standard 864, 9th Edition
  • Backlit 80-character LCD display (20 characters x 4 lines)
  • Mimics all display information from the host panel
  • Control switches for Signal Silence, System Acknowledge, Reset, and Drill
  • Control switches can be independently enabled or disabled at the FACP
  • Keyswitch enables/disables control switches and mechanically locks annunciator enclosure
  • Keyswitch can be enabled or disabled at the FACP
  • Enclosure supervised for tamper
  • System status LEDs for AC Power, Alarm, Trouble, Supervisory, and Alarm Silence
  • Local sounder can be enabled or disabled at the FACP
  • N-ANN-100 connects to the ANN-BUS terminal on the FACP and requires minimal panel programming
  • Displays device type identifiers, individual point alarm, trouble, supervisory, zone, and custom alpha labels
  • Time-and date display field
  • Surface-mount or flush-mount installation options
  • Optional trim ring for a more finished look
  • Can be remotely located up to 6,000 feet (1,800 m) from the panel
  • Backlight turns off during AC loss to conserve battery power but will turn back on if an alarm condition occurs
  • May be powered by 24 VDC from the host FACP or by remote power supply (requires 24 VDC)
  • Up to eight N-ANN-100s can be connected on the ANN-BUS

N-ANN-100 80 Character LCD Remote Fire Annunciator

Download

Notifier - Data Sheet