Notifier N-ANN-80-W

$554.67

80-Character Serial LCD Annunciator; White

Availability: In Stock

Condition: New
Brand: Notifier
Status: Active
SKU: 125931
Manufacturer Part #: N-ANN-80-W

Description

The N-ANN-80 annunciator is a compact, backlit, 80-character LCD fire annunciator that mimics the Fire Alarm Control Panel (FACP) display. It provides system status indicators for AC Power, Alarm, Trouble, Supervisory, and Alarm Silenced conditions. The N-ANN80 and the FACP communicate over a two-wire serial interface employing the ANN-Bus communication format. Connected devices are powered, via two additional wires, by either the host FACP or a remote UL-listed, filtered power supply. The N-ANN-80 is black; for white order N-ANN-80-W.

Additional information

Weight 2.00 lbs
Dimensions 1.37 × 6.87 × 5.37 in
Manufacturer

Honeywell

Brand

Condition

New

Unit of Measurement

EA (Each)

Production Status

Active

Listings & Approvals

CSFM, FM, MEA, UL

Features

  • Backlit 80-character LCD display (20 characters x 4 lines)
  • Mimics all display information from the host panel
  • Control switches for System Acknowledge, Signal Silence, Drill, and Reset
  • Control switches can be independently enabled or disabled at the FACP
  • Keyswitch enables/disables control switches and mechanically locks annunciator enclosure
  • Keyswitch can be enabled or disabled at the FACP
  • Enclosure supervised for tamper
  • System status LEDs for AC Power, Alarm, Trouble, Supervisory, and Alarm Silence
  • Local sounder can be enabled or disabled at the FACP
  • N-ANN-80 connects to the ANN-Bus terminal on the FACP and requires minimal panel programming
  • Displays device type identifiers, individual point alarm, trouble, supervisory, zone, and custom alpha labels
  • Time-and date display field
  • Surface mount directly to wall or to single, double, or 4″ square electrical box
  • Semi-flush mount to single, double, or 4″ square electrical box. Use ANN-SB80KIT for angled view mounting
  • Can be remotely located up to 6,000 feet (1,800 m) from the panel
  • Backlight turns off during AC loss to conserve battery power but will turn back on if an alarm condition occurs
  • May be powered by 24 VDC from the host FACP or by remote power supply (requires 24 VDC)
  • Up to eight N-ANN-80s can be connected on the ANN-Bus

N-ANN-80; 80-Character Serial LCD Annunciator

Download

Notifier - Data Sheet