Description
Designed for use on a Siemens Modular (or FireFinder XLS) control panel, the Zone Indicating Card (Model ZIC-8B) provides eight (8) fully supervised programmable output circuits. Model ZIC-8B supplies eight (8) Class B (Style Y) type output circuits, power limited to 2.0 amps maximum per circuit. Each circuit can be independently programmed for use with listed audible or visual notification appliances, or with listed emergency audio speakers. Model ZIC-8B plugs into one (1) slot in a Model CC-5 or CC-2 card cage, and has on-board light-emitting diodes (LEDs) for system status and troubleshooting. Indication of power, communication, internal operation, and ground-fault conditions are provided, as well as indication of circuit activation or Trouble system conditions. System-status conditions are also reported to the panel’s central processor unit.