Description
Viking supervised VXD Single-Interlocked Preaction Systems utilize a Viking Model VXD Deluge Valve and a pneumatically pressurized automatic sprinkler system. This feature helps prevent undetected leaks. Single-Interlocked Preaction Systems are commonly used where the sprinkler system piping and/or sprinklers may be subject to damage. If the system piping or a sprinkler is damaged, supervisory pressure is reduced and a “low air” supervisory condition is activated. The Pneumatically controlled preaction systems require a pneumatic release system, equipped with thermostatic (rate-of-rise) releases, fixed-temperature releases, and/or pilot sprinkler heads. Release trim for the pneumatically controlled deluge valve includes a pneumatic actuator normally held closed by the air/nitrogen pressure maintained in the pneumatic release system.
Reviews
There are no reviews yet.