In stand-alone or network configurations, Honeywell’s XLS120 meets virtually every application requirement.

The XLS120‘s modular design makes system planning easier. The panel can be configured with just a few devices for small building applications, or networked with many devices to protect a large campus or a high-rise office block. Simply add additional peripheral equipment to suit the application.

For installations using XLS120C, an optional ACM Series annunciator can be mounted in the same cabinet (up to 48 zones/points, order separately).

When combined with a Honeywell Enterprise Buildings Integrator (EBI), the XLS120 becomes part of an owner-operated proprietary monitoring system, allowing the connection of standalone or networked panels.

Additional information

Weight 16 lbs
Manufacturer

Honeywell

Brand

Condition

New

Type

Control Panel

Style

Addressable

Color

N/A

Series

Production Status

Obsolete

Compatibility

Features

  • Certified for seismic applications when used with the appropriate seismic mounting kit.
  • One isolated intelligent Signaling Line Circuit (SLC) Style 4, 6 or 7.
  • Up to 159 detectors (any mix of ion, photo, thermal, or multi-sensor) and 159 modules (Addressable pull stations, normally open contact devices, two-wire smoke, notification, or relay). 318 devices maximum.
  • Standard 80-character display.
  • Network options:
    • High-speed network for up to 200 nodes (XLS3000, XLS140-2, XLS140, XLS120(C), XLS-NCA/-NCA2 Network Annunciator, or XLS-DVC, and Honeywell Enterprise Buildings Integrator [EBI]).
    • Standard network for up to 103 nodes (XLS3000, XLS140-2, XLS120(C), XLS-NCA2 Network Annunciator, or XLS-DVC, and Honeywell Enterprise Buildings Integrator [EBI]). Up to 54 nodes when DVC is used in network paging.
  • 6.0 A power supply with four Class A/B built-in Notification Appliance Circuits (NAC). Selectable System Sensor, Wheelock, or Gentex strobe synchronization.
  • Built-in Alarm, Trouble, Security, and Supervisory relays.
  • Autoprogramming and Walk Test reports.
  • Optional universal 318-point DACT.
  • 80-character remote annunciators (up to 32).
  • EIA-485 annunciators, including custom graphics.
  • Printer interface (80-column and 40-column printers).
  • History file with 800-event capacity in nonvolatile memory, plus separate 200-event alarm-only file.
  • Alarm Verification selection per point, with tally.
  • Presignal/Positive Alarm Sequence (PAS).
  • Silence inhibit and Auto Silence timer options.
  • NAC coding functions:
    • March time.
    • Temporal.
    • California two-stage coding.
    • Canadian two-stage.
    • Strobe synchronization.
  • Field-programmable on panel or on PC, with VeriFire® Tools program check, compare, simulate.
  • Full QWERTY keypad.
  • Battery charger supports 18 – 200 AH batteries.
  • Non-alarm points for lower priority functions.
  • Remote ACK/Signal Silence/System Reset/Drill via monitor modules.
  • Automatic time control functions, with holiday exceptions.
  • Extensive, built-in transient protection.
  • Powerful Boolean logic equations.

XLS120(E)(C): Intelligent Addressable Fire Alarm System